2.4
PARAMETER SEQUENCE
The Program Mode parameter sequence is as follows:
2-3
Volume I
OM091-2
59136
Parameter
Description
(Primary
Display)
Parameter
Description
Adjustment Range
Scaling
Point 1
The first sensor input value
point (expressed as a
percentage of input span)
which is used to establish
a curve for scaling sensor
input values into
engineering unit values.
0.00% to 100.00%
0.00%
Display
Point 1
The engineering unit value
corresponding to Scaling
Point 1.
−
19999 to 99999
0.00
Scaling
Point 2
The second sensor input
value point (expressed as
a percentage of input
span) which is used to
establish a curve for
scaling sensor input
values into engineering
unit values.
0.00% to 100.00%
100.00%
Display
Point 2
The engineering unit value
corresponding to Scaling
Point 2.
−
19999 to 99999
100.00
The scaling process can be continued up to a total of 10 Scaling Points and 10 Display Points,
until a Scaling Point is given the value 100.0%; this will be the final Scaling Point/Display Point
offered. NOTE: Ensure that Scaling Point 1
≤
Scaling Point 2
≤
Scaling Point 3 etc.
Decimal
Point
Position
Defines the decimal point
position for displayed
process variable and
alarm values.
0 to 0.0000
0.0
Re-
transmission
Scale
Minimum
The lower end of the linear
scale for the
re-transmission output,
expressed as the value
corresponding to the
minimum output signal.
−
19999 to 99999
-19999
Re-
transmission
Scale
Maximum
The upper end of the
linear scale for the
re-transmission output,
expressed as the value
corresponding to the
maximum output signal.
-19999 to 99999
99999
Process
Variable
Offset
Corrects a known offset of
the input in order to
display more accurately
the process value.
−
19999 to 99999
0.00