19
4. Technical Specifications
4.1 General Specifications
Detected Gases: Simultaneous detection of C
1
-C
8
flammable gases
Detection Distance range:
Table 11: Detection Distance Range
Model No.
301
302
Distance (ft)
2-11.5
9.8-49
Distance (m)
0.6-3.5
3-15
Response Time
2 Sec.
10 Sec.
Spectral Response:
3.0 - 4.0 micron
Sensitivity Range:
Table 12: Sensitivity Range
Field of View:
Line of Sight
Alignment Tolerance:
± 2°
Drift:
Long term ± 5% of full scale
Temperature Range:
-40°F (-40°C) to +158°F (+70°C)
Immunity to false alarm:
Does not produce false alarm by Hydrocarbon
Flames and must of IR Radiation Sources.
301
302
Standard
0-2.5 LEL.m
0-5 LEL.m
DIPswitch
0-1 LEL.m
0-2 LEL.m