Spectrex Series 300 Open-Path Gas Detection System User Manual
Page 19
Spectrex Inc. - SafEye
TM
300 Gas Detector Manual – TM 794100, Rev. D, May 2004
11
Table 4. Standard (default) 4-20mA Current for the Gas Channel
Current
Status and Description
0mA +0.5mA
Fault 2 or Low Voltage
2mA ±0.5mA
Fault 1
4mA ±0.5mA
Zero reading - No gas detected
4-20mA
Continuous measuring of gas concentration at a range
between 0 and 5 LEL.m or full scale
21mA
Concentration is over the range limit (more than full scale
concentration).
Table 5. Discrete reading of 4-20mA at different detector’s modes
LEL.m Setting
Current Reading
Mode
301
302
0 +0.5mA
Fault 2 or Low Voltage
-
-
2 ±0.5mA
Fault 1
-
-
4 ±0.5mA
Standby
0
0
14 ±0.5mA
Warning
0.6
1
19 ±0.5mA
Alarm
1
2.5
3.7.2 Relays
The detector includes three relays:
•
Fault relay
•
Alarm relay
•
Accessory relay
Fault Relay contacts are normally energized closed, and opened when in Fault
condition
3.7.3 RS-485 Interface
The RS-485 input/output sends complete data information to a PC and receives
data or control commands from the PC. The communication with the PC is
operated through this interface is executed only when used with appropriate host
software.
The following PC minimal hardware requirements are as follows:
•
386 PC using DOS Ver. 5.0 or higher
•
1 MB RAM.
•
2 MB free hard disk space.
•
1.2 or 1.44 MB floppy drive
•
Color VGA
•
RS-485 Interface Card to be defined as COM1 or COM2. Isolated Adapter
is preferred.