Table 10 describes SW3 DIPswitches position and the required function for
setting the detector according to the necessary configuration
Table 10. SW3 DIPswitches Configuration
Switch
No.
Off position
On position
Default
setting
1
Non latching Alarm
Relay
Alarm Relay latches. Latching reset
can be provided by momentarily power
disconnection or when the detector is
set to alignment mode.
off
2
Continuous reading
of the 4-20mA
output reading
Discrete Reading of the 4-20mA output
according to the detector status (see
table 5).
off
3
Non-latching Alarm
indications during
Blocking Mode
Alarm indications are latched when the
detector turns to Blocking Mode from
Alarm position. Latching reset can be
provided only if the detector turns to
Normal Mode.
off
4
Normal Position
(open)
Communication line termination for
impedance matching
off