beautypg.com

Spectrex Series 300 Open-Path Gas Detection System User Manual

Page 26

background image

Spectrex Inc. - SafEye

TM

300 Gas Detector Manual – TM 794100, Rev. D, May 2004

18

Table 10 describes SW3 DIPswitches position and the required function for
setting the detector according to the necessary configuration

Table 10. SW3 DIPswitches Configuration

Switch

No.

Off position

On position

Default

setting

1

Non latching Alarm
Relay

Alarm Relay latches. Latching reset
can be provided by momentarily power
disconnection or when the detector is
set to alignment mode.

off

2

Continuous reading
of the 4-20mA
output reading

Discrete Reading of the 4-20mA output
according to the detector status (see
table 5).

off

3

Non-latching Alarm
indications during
Blocking Mode

Alarm indications are latched when the
detector turns to Blocking Mode from
Alarm position. Latching reset can be
provided only if the detector turns to
Normal Mode.

off

4

Normal Position
(open)

Communication line termination for
impedance matching

off