Spectrex 20/20SH - Hydrogen Flame Detector User Manual
Page 26
Spectrex Inc. - SharpEye
TM
Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005
18
E. Electrical outputs
• Dry Contact Relays:
Table 9: Contact Ratings
Relay
Name
Type
Normal
position
Maximum Ratings
Alarm
SPDT N.O. N.C. 2A at 30VDC or 0.5A at 250 VAC
Accessory SPST N.O.
5A at 30VDC or 250 VAC
Fault
SPST N.C.
5A at 30VDC or 250 VAC
• 4-20mA Current Output:
Terminals 11 and 12:
STATE
Output
FAULT
0 + 0.5mA
BIT FAULT
2mA±10%
NORMAL
5mA±10%
WARNING 10mA±5%
ALARM
15mA±5%
• Communication Network:
The detector is equipped with an RS-485 communication link that can
be used in installations with computerized controllers.
The communicator protocol is compatible with the Modbus
communicator protocol.
o
This protocol is a standard and widely used.
o
It enables continuous communication between a single standard
Modbus controller (Master device) and a serial Network of up to
247 detectors.
o
It enables connection between different types of Spectrex detectors
or other
o
Modbus devices to the same Network.