Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 20

background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

12

4.3.1 Function Setup

The user can select the desired mode of operation by means of host.

Table 6: Function Setup

Name

Yes

No

1

Alarm Latch

Alarm latching enable

Alarm latching disable
(default)

2

Accessory Relay Accessory Relay activate at

warning level

Accessory Relay activate
at Alarm level (default)

3

Automatic BIT

Automatic & manual bit
(default)

Manual bit only

4

Alarm BIT

Successful manual bit
activates the Alarm Relay for
approximately 3 seconds
(default)

Successful manual bit
does not activate the
Alarm Relay

5

Accessory BIT

Successful manual bit
activates the Accessory Relay
for approximately 3 seconds
(default)

Successful manual bit
does not activates the
Accessory Relay

6

EOL

Accessory Relay is used as
End of Line

Accessory Relay operates
in accordance with
Function 2 and 5 (default)

4.3.2 Sensitivity Ranges

The detector offers four (4) sensitivity settings. The settings refer to the Hydrogen
plume fire with 20” (0.5m) height and 8” (0.2m) width, from low sensitivity of 16 ft.
(5m) to 100 ft. (30m). For other types of fuel sensitivity, refer to table 2.

Table 7: Sensitivity range

##

Sensitivity

1

16 ft. (5m)

2

33 ft. (10m)

3

66 ft. (20m)

4*

100 ft. (30m)

* Default