Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 17

background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

9

4.2 Output Signals

The detector controls the following outputs:

• Alarm relay

• Accessory relay

• Fault relay

• 4-20mA current output

• RS-485 communication


The detector can be in one of the following states.
Normal:

The detector is functioning normally.

BIT:

The detector performs a Built-In-Test.

Warning:

Fire detected - changed to warning – pre-alarm state.

Alarm:

Fire detected - changed to fire alarm state.

Latched Alarm
(Optional)

The alarm outputs are latched due to the detection of a fire that
has already been extinguished.

BIT Fault:

A fault is detected during BIT sequence. The detector will
continue to detect fire if the alarm conditions occur.

Fault:

A fault is detected when the power supply is too low or during a
software fault.


In each state the detector will activate different outputs as specified in table 5.

Table 5: Output Signals Versus Detector State

Detector
State

Power
Led

Alarm
Led

Alarm
Relay

Accessory
Relay

Fault
Relay

4-20mA
Output

Normal

On Off

Off

Off On

5mA

Warning

On Flash

2Hz

Off On

(1)

On

10mA

Alarm

(4)

On On On

On On

15mA

Latch

(2)

On On On

Off On

15mA

On On On

On

(1)

On

15mA

BIT Fault

(3)

Flash Off

Off Off

Off

2mA

Warning at
BIT Fault

Flash
4Hz

Flash
4Hz

Off On

(1)

Off

10mA

Alarm at BIT
Fault

Flash
4Hz

On

On On

Off 15mA

Fault

Flash
4Hz

Off Off

Off Off

0mA


Note:
1 Accessory relay can be activated at warning level or alarm level depending on

programmable function

2 The Alarm state can be latched according to programmable function
3 The detector will be in its BIT FAULT state until it has passed a successful BIT.