Spectrex 20/20SH - Hydrogen Flame Detector User Manual
Page 23
Spectrex Inc. - SharpEye
TM
Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005
15
D. Automatic & Manual BIT
Manual Bit
Functions as described in Paragraph 4.4.C. In the case of an unsuccessful BIT all
outputs will function as described in Paragraph. 4.4.C, but the BIT will be
automatically executed every 1-minute. This mode of operation will continue until
successful Bit has been encountered. As a result, the detector will resume its
normal operation.
Automatic BIT
The detector automatically performs a BIT every 60 minutes.
A successful BIT sequence does not activate any indication:
The FAULT relay
is CLOSED (NORMAL).
The POWER LED
is ON (NORMAL).
The 4-20mA Output
Indicate NORMAL (5mA).
An unsuccessful BIT sequence activates the following:
The FAULT relay
is opened.
4-20mA output
indicate BIT FAULT (2mA).
The POWER LED (yellow) flashes (4 Hz).
BIT procedure
will be performed every 1 minute.