Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

15

D. Automatic & Manual BIT

Manual Bit
Functions as described in Paragraph 4.4.C. In the case of an unsuccessful BIT all
outputs will function as described in Paragraph. 4.4.C, but the BIT will be
automatically executed every 1-minute. This mode of operation will continue until
successful Bit has been encountered. As a result, the detector will resume its
normal operation.

Automatic BIT
The detector automatically performs a BIT every 60 minutes.

A successful BIT sequence does not activate any indication:

The FAULT relay

is CLOSED (NORMAL).

The POWER LED

is ON (NORMAL).

The 4-20mA Output

Indicate NORMAL (5mA).


An unsuccessful BIT sequence activates the following:

The FAULT relay

is opened.

4-20mA output

indicate BIT FAULT (2mA).

The POWER LED (yellow) flashes (4 Hz).
BIT procedure

will be performed every 1 minute.