beautypg.com

Spectrex 20/20SH - Hydrogen Flame Detector User Manual

Page 14

background image

Spectrex Inc. - SharpEye

TM

Hydrogen (SH) Flame Detector Manual – TM 784600, Rev. A, May 2005

6

Other fuels
The detector will react to other types of fires as follows:
Fire Size:

Methanol and ethanol - 1ft

2

(0.1m

2

) pan fire


Maximum Wind Speed: 6.5 ft/sec (2 m/sec)
Maximum Response Time: 10 sec

Table 2: Response Sensitivity for other Fuels

Type Of Fuel

% of Max. Distance

Hydrogen 100%
Ethanol 62%
Methanol 26%

3.2 Cone Of Vision


Horizontal: 90°
Vertical: 90°

Figure 3: Horizontal and Vertical Fields of View