3. Performance

3.1 Detection Sensitivity

Detection sensitivity is the maximum distance at which the detector will reliably
detect a specific size of fire & typical type of fuel (standard fire).

Standard Fire:
Gases – define by a plume fire with 20” (0.5m) height and 8” (0.2m) width
or
Liquid - 1ft

2

(0.1m

2

) pan fire


Wind speed of 6.5 ft/sec (2 m/sec).

Sensitivity Ranges:
The detector has four user selectable sensitivity ranges. For each range there are
two response levels.

1. WARNING (Pre-alarm)
2. ALARM


The detection distance, for the WARNING level, is approximately 10% higher than
the ALARM distance.

Alarm response times for a “standard fire” at a specified range are shown
hereunder.

Table 1: Alarm Response Time Versus Range

Sensitivity

1

2

3

4

Range – ft (m)

16 (5)

33 (10)

66 (20)

100 (30)

Response Time (sec)

3 5 8 10

* These results refers to Hydrogen

For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for
the detector is 0.005 (1/meter).

Note:

Zeta parameters may vary significantly with changes in temp, air pressure,
humidity, visibility conditions, etc.