5.2.2 Wiring Check
(1) Insert the Test Lead into the instrument.(Fig.15)
(2) Connect test lead to object to be tested.(Fig.11,12,13,14)
(3) Make sure that the P-E and P-N wiring Check LEDs are lit and the
wiring in correct LED is not lit. If it is not correct, disconnect the
tester and check the wiring for a possible fault.
5.2.3 Testing
(1) Press the test button. A beep will sound as the test is conducted and
the value of loop impedance will be displayed.
Note: When Test Lead removed during a measurement, "no" is
displayed on LCD and a measurement will be stopped. Please
check Test Lead is rightly connected.
● LOOP range
● PSC range
LOOP Range
PSC Range
2000Ω
200A
The Initial value
#
CAUTION
The RCD of a circuit shall be bypassed when measuring on LOOP 20
Ω range. Do not operate the Test button on RCD while RCD is
bypassed. Be sure to get back the bypassed RCD after test.
Fig.15
- 1009 (13 pages)
- 1011 (12 pages)
- 1012 (12 pages)
- 1018 (1 page)
- 1030 (1 page)
- 1061 (58 pages)
- 1051 (40 pages)
- 1109S (36 pages)
- 1110 (1 page)
- 2000 (1 page)
- 2002PA (27 pages)
- 2007A (1 page)
- 2009R (33 pages)
- 2012R (2 pages)
- 2017 (1 page)
- 2031 (1 page)
- 2033 (9 pages)
- 2040 (2 pages)
- 2046R (2 pages)
- 2200 (3 pages)
- 2210R (1 page)
- 2300R (1 page)
- 2413F (24 pages)
- 2413R (24 pages)
- 2431 (2 pages)
- 2432 (1 page)
- 2433R (1 page)
- 2434 (10 pages)
- 2500 (1 page)
- 2608A (2 pages)
- 3005A (24 pages)
- 3021 (24 pages)
- 3121A (12 pages)
- 3126 (28 pages)
- 3127 (60 pages)
- 3128 (88 pages)
- 3131A (20 pages)
- 3132A (20 pages)
- 3161A (24 pages)
- 3321A (24 pages)
- 4105A (10 pages)
- 4106 (48 pages)
- 4116A (20 pages)
- 4140 (32 pages)
- 4200 (24 pages)