KYORITSU 6050 User Manual
Page 19
̶ 17 ̶
Practical example of verification of the protection is a TT system
according to the international Standard IEC 60364.
Fig.12
The maximum value of Zs for this example is 2.1Ω(16amp gG fuse,0.4
seconds).The loop tester reads 1.14Ωand consequently the condition
Zs<_Uo / la is met.
5.1.2 Principles of the Measurement of Line Impedance and
Prospective Short Circuit Current
Line impedance is the impedance, which is measured between Phase-
terminal L and Neutral-terminal N of single-phase system, or between
two phases of three-phase system. Measurement principal used in this
instrument is the same as it for Fault loop impedance measurement, but
measurement is performed between Terminal L and N, or between two
phases.
Breaking current capacity of installed over-current protection devices
should be higher than Prospective Short-Circuit current, otherwise it is
necessary to change the rated current of involved over-current
protection device.
- 1009 (13 pages)
- 1011 (12 pages)
- 1012 (12 pages)
- 1018 (1 page)
- 1030 (1 page)
- 1061 (58 pages)
- 1051 (40 pages)
- 1109S (36 pages)
- 1110 (1 page)
- 2000 (1 page)
- 2002PA (27 pages)
- 2007A (1 page)
- 2009R (33 pages)
- 2012R (2 pages)
- 2017 (1 page)
- 2031 (1 page)
- 2033 (9 pages)
- 2040 (2 pages)
- 2046R (2 pages)
- 2200 (3 pages)
- 2210R (1 page)
- 2300R (1 page)
- 2413F (24 pages)
- 2413R (24 pages)
- 2431 (2 pages)
- 2432 (1 page)
- 2433R (1 page)
- 2434 (10 pages)
- 2500 (1 page)
- 2608A (2 pages)
- 3005A (24 pages)
- 3021 (24 pages)
- 3121A (12 pages)
- 3126 (28 pages)
- 3127 (60 pages)
- 3128 (88 pages)
- 3131A (20 pages)
- 3132A (20 pages)
- 3161A (24 pages)
- 3321A (24 pages)
- 4105A (10 pages)
- 4106 (48 pages)
- 4116A (20 pages)
- 4140 (32 pages)
- 4200 (24 pages)