KYORITSU 6050 User Manual
Page 10
̶ 8 ̶
● UL value selector
Select UL (limit of contact voltage value) 25V
or 50V. Where Uc (contact voltage) exceeds
UL value at RCD testing, "Uc H" will be
displayed without starting the measurement.
● Voltage Indication
When connecting Test Lead to circuit, voltage
between L-PE is displayed. If the voltage is
lower than 100V, displayed as "V L-PE Lo".
And if it is higher than 260V, displayed as "V L-
PE Hi".But on L-L measurement range,
displayed as "V L-PE Hi" if the voltage is 440V
or more.
● Low battery
warning
" "symbol appears in the display if the battery
voltage drops below 8V.
● Auto power off
Automatically switches the instrument off after
a period of approximately 10 minutes.
● Display
The liquid crystal display has 3 1/2 digits with a
decimal point and units of measurement (V,
Ω,A,kA,mA,ms )
● Data memory,
Communication
facility
Can store 300 measured result.
Data can be transferred to PC via Optical
Adapter Model 8212.
● Optional
Accessory
1) Model 7121 for measuring distribution board
or lighting circuit test lead.
2) Optical Adapter Model 8212 (with PC
software "Kew Report")
● Auto Test
Instrument becomes Auto test mode by turning
Test button to right and locked it. Under Auto
test mode, test starts automatically only by
connecting Test Lead to a measuring circuit.