Digital output
4.4 Electrical connection data for use in hazadous areas
Ex tD A20 IP67 100
Ex tD A20 IP67 100
Ex tD A20 IP67 100
Ex tD A20 IP67 100°C
C
C
C
The LS 6500 must be installed in accordance with prevailing guidelines for zone 20 without
without
without
without a
barrier.
Supply range: 12...30 VDC, max. 100 mA
Temperature class: T100; refer to following table
Ex nA II T 5 (pending)
Ex nA II T 5 (pending)
Ex nA II T 5 (pending)
Ex nA II T 5 (pending)
The LS 6500 must be installed in accordance with prevailing guidelines for zone 2 without
without
without
without a
barrier.
Supply range: 12...30 VDC, max. 100 mA
Temperature class: T1...T5; refer to following table
Ex ia IIC T5 (pending)
Ex ia IIC T5 (pending)
Ex ia IIC T5 (pending)
Ex ia IIC T5 (pending)
The LS 6500 must be installed in accordance with prevailing guidelines for zone 0 with
with
with
with a barrier.
A certified Ex ia or isolation barrier with the max. values
U
max
= 30 VDC,
I
max
= 0.1 A,
P
max
= 0.75 W
must be used.
Supply range: 12...30 VDC, max. 100 mA
Temperature class: T1...T5; refer to following table
Normally open
Normally closed
M16
M16
1 PLC
2 active high
1 PLC
2 active low