ELECTRICAL CONNECTIONS

4

17

LS 6500

www.krohne.com

03/2013 - 4000649103 - MA LS 6500 R03 en

Digital output

4.4 Electrical connection data for use in hazadous areas

Ex tD A20 IP67 100

Ex tD A20 IP67 100

Ex tD A20 IP67 100

Ex tD A20 IP67 100°C

C

C

C

The LS 6500 must be installed in accordance with prevailing guidelines for zone 20 without

without

without

without a

barrier.
Supply range: 12...30 VDC, max. 100 mA
Temperature class: T100; refer to following table

Ex nA II T 5 (pending)

Ex nA II T 5 (pending)

Ex nA II T 5 (pending)

Ex nA II T 5 (pending)

The LS 6500 must be installed in accordance with prevailing guidelines for zone 2 without

without

without

without a

barrier.
Supply range: 12...30 VDC, max. 100 mA
Temperature class: T1...T5; refer to following table

Ex ia IIC T5 (pending)

Ex ia IIC T5 (pending)

Ex ia IIC T5 (pending)

Ex ia IIC T5 (pending)

The LS 6500 must be installed in accordance with prevailing guidelines for zone 0 with

with

with

with a barrier.

A certified Ex ia or isolation barrier with the max. values
U

max

= 30 VDC,

I

max

= 0.1 A,

P

max

= 0.75 W

must be used.
Supply range: 12...30 VDC, max. 100 mA
Temperature class: T1...T5; refer to following table

Normally open

Normally closed

M16

M16

1 PLC

2 active high

1 PLC

2 active low