Technical data, 2 technical data – KROHNE OPTIBAR P 3050 C EN User Manual

Page 36

background image

7

TECHNICAL DATA

36

OPTIBAR P 3050 C

www.krohne.com

03/2012 - 4001953401 - MA OPTIBAR P3050C R02 en

7.2 Technical data

INFORMATION!

The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local representative.

Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).

Measuring system

Measuring principle

Metallic diaphragm with piezoresistive measuring cell

Application range

Measurement of absolute and gauge pressure of gases, vapours and liquids

Measuring ranges

Measuring ranges

Measuring ranges

Measuring ranges

Absolute pressure

Pressure ranges [bara]: 0…0.5; 0…1; 0…5; 0…10; 0…40; 0…100; 0…200

Pressure ranges [psia]: 0…7.25; 0…14.5; 0…72.5; 0…145; 0…580; 0…2900

Gauge pressure

Pressure ranges [barg]: 0…0.2; 0…0.5; 0…1; 0…2; 0…5; 0…10; 0…20

Pressure ranges [psig]: 0…2.9; 0…7.25; 0…14.5; 0…29; 0…72.5; 0…145;

0…290

Design

Blind version

Position correction, zero and measurement span adjustment of span start

(4 mA) and span end (20 mA) with push button on the converter electronics.

Version with display (optional)

LCD graphic display with 4 push buttons.

Resolution: 128 x 64

User languages: German, English and French (in preparation)

Measuring accuracy

Reference conditions acc. to

IEC 60770

Ambient temperature (constant): +18...+30°C / +64...+86°F

Relative humidity (constant): 30...80%

Ambient pressure (constant): 950...1060 mbar / 14.8...15.4 psi

Filling: silicone oil

Measuring accuracy

In relation to non-linearity, hysteresis and repeatability

±

0.1% of measuring span

Long-term stability acc. to

DIN EN 61298-1

≤±0.1% within 1 year

Response time acc. to IEC 61298-1

T(95%) = 50 ms (incl. dead time)