OPERATION

5

23

OPTIBAR P 3050 C

www.krohne.com

03/2012 - 4001953401 - MA OPTIBAR P3050C R02 en

Operation

5.1 Start-up

The pressure transmitter may only be started up after it has been completely installed and
checked by appropriately qualified personnel. Switch on the operating voltage for start-up. Prior
to applying the operating voltage, it is crucial to check the correctness of the process connection
and the electrical connection and ensure that the impulse line has been completely filled with
the process medium. Then proceed with start-up. If available, the shut-off fixtures are to be
activated in the following sequence (all valves are closed in the base setting):

• Open extraction shut-off valve, if any.
• Open shut-off valve, if any.

For shut-down reverse the order.

5.2 Factory settings and settings during reset

The pressure transmitter factory settings can be based on a measuring span specified by the
customer in the order. This and other information is located on the device nameplate. If the
customer has not specified any settings, the device always leaves the factory with the following
settings:

[*] only with optional LCD display

During a reset (which can be selected using the keyboard on the display), the pressure
transmitter is automatically started with the above factory settings.

For a factory reset without LCD display, push the push button on the converter electronics for
more than 30 seconds.

INFORMATION!
Please note that absolute pressure transmitters with measuring ranges ≤100 kPa abs. (1 bara)
were affected by the externally present atmospheric pressure during transport and storage. A
warm-up period of several hours following start-up is therefore required in order to reach the
specified accuracy.

Device parameter

Factory pre-setting

Lower range limit (zero point)

4 mA

Upper range limit (URL)

20 mA

Alarm current

High alarm 21 mA

Damping

0.1 s

Main display value [*]

Pressure value in % URL

Sensor temperature [*]

Indication in K

Write protection [*]

No

Language [*]

English

Contrast [*]

50%

Bargraph indication [*]

Yes