Technical data – KROHNE OPTIFLUX 7300 EN User Manual
Page 30
6
TECHNICAL DATA
30
OPTIFLUX 7300
www.krohne.com
01/2011 - 4001163301 - MA OPTIFLUX 7300 R01 en
HART
HART
HART
HART
®
Description
HART
®
protocol via active and passive current output.
HART
®
version: V5
Universal HART
®
parameter: completely integrated
Load
≥ 250 Ω at HART
®
test point.
Note maximum load for current output!
Multidrop operation
Yes, current output = 4mA
Multidrop address adjustable in operation menu 1...15
Device driver
Available for FC 375, AMS, PDM, FDT/DTM
Registration
(HART
®
Communication
Foundation)
Yes
Pulse or frequency output
Pulse or frequency output
Pulse or frequency output
Pulse or frequency output
Output data
Pulse output: volume flow, mass flow
Frequency output: volume flow, mass flow, diagnostic value, flow velocity,
coil temperature
Function
Adjustable as pulse of frequency output.
Pulse rate/frequency
0.01...10000 pulses/s or Hz
Settings
Pulses per volume or mass unit or max. frequency for 100% flow.
Pulse width: adjustable as automatic, symmetric of fixed
(0.05...2000 ms)
Operating data
Basic I/Os
Basic I/Os
Basic I/Os
Basic I/Os
Modular I/Os
Modular I/Os
Modular I/Os
Modular I/Os
Ex i
Ex i
Ex i
Ex i
Active
U
nom
= 24 VDC
f
max
in operating menu
set tof
max
≤ 100 Hz:
I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U
0, nom
= 24 V
at I = 20 mA
f
max
in operating menu
set to 100 Hz
< f
max
≤ 10 kHz:
I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U
0, nom
= 22.5 V
at I = 1 mA
U
0, nom
= 21.5 V
at I = 10 mA
U
0, nom
= 19 V
at I = 20 mA