TECHNICAL DATA

6

29

OPTIFLUX 5000

www.krohne.com

10/2011 - 4000686202 - MA OPTIFLUX 5000 SW R02 en

6.3 Measuring accuracy

Each flowmeter is standard wet calibrated under reference conditions by direct volume
comparison before leaving the factory.

Reference conditions

• Medium: water
• Temperature: 20°C / 68°F
• Pressure: 1 bar / 14.5 psi

In combination with the IFC 300

In combination with the IFC 100

Figure 6-1:
X

XX

X [m/s]: flow velocity
Y

YY

Y[%]: deviation from the actual measured value (mv)

Accuracy

Curve

DN2.5...6 / 1/10...1/4"

0.3% of mv + 2 mm/s

3

DN10...100 / 3/8... 4"

0.15% of mv + 1 mm/s

1

Accuracy

Curve

DN2.5...6 / 1/10...1/4"

0.4% of mv + 1 mm/s

As 2 + 0.1%

DN10...100 / 3/8...4"

0.3% of mv + 1 mm/s

2