Establish rs485 connection – KROHNE MFC 400 Modbus User Manual
Page 7
ESTABLISH RS485 CONNECTION
4
7
MFC 400
www.krohne.com
05/2013 - 4002525102 - AD Modbus MFC 400 R02 en
To establish a RS485 connection with the signal converter, prepare the master device with the
appropriate default settings or use custom parameters specified via display of the signal
converter.
The Modbus RS485 settings can be found in the menu C6.8 of the display. The following
parameters can be configured:
These settings can be changed via Modbus too. For further information refer to
Modbus RS485
Communication Settings
on page 24.
All devices connected to the bus, must have the same baud rate.
Parameter
Legal values
Default values
Display Fct. No.
Slave address
1...247
1
C6.8.1
"Baude rate"
1200, 2400, 3600, 4800, 9600,
19200, 38400, 57600, 115200
bps
19200 bps
C6.8.2
Parity
Even, Odd, No
Even Parity
C6.8.3
Data format
Big Endian, Little Endian
Big Endian
C6.8.4
Transmission
delay
0...0.04 [s]
0 s
C6.8.5
Stop Bits
1 Stop Bit, 2 Stop Bits
1 Stop Bit
C6.8.6
INFORMATION!
It is of great importance to ensure at the time of the procedure of devices addressing, that there
are not two devices with the same address. In such a case, an abnormal behaviour of the whole
serial bus can occur. It is then impossible for the master to communicate with all present slaves
on the bus.