Modbus protocol – KROHNE MFC 400 Modbus User Manual

Page 25

background image

MODBUS PROTOCOL

5

25

MFC 400

www.krohne.com

05/2013 - 4002525102 - AD Modbus MFC 400 R02 en

5.8.14 NAMUR NE 107 Variable Event Group(s)

The following eight event groups can be mapped to any status signal.

For further information refer to section "Status messages and diagnostic information" in the
signal converter standard manual.

Legal values for those registers:

• 128: Failure (F)
• 32: Out Of Specification (S)
• 16: Function Check (C)
• 4: Maintenance Request (M)
• 1: Information (I)

Modbus Function Codes "Read Holding Registers" (0x03) and "Write Multiple Registers" (0x10)

Holding
Register

Description

Status Group

Type

No. of
registers

Default Value

Display
Fct. No.

52016

52016

52016

52016

(0xCB30)

Status Signal of

Event Group 15

Proc: Current Input

Byte

1

128

Failure (F)

C1.5.9

52017

52017

52017

52017

(0xCB31)

Status Signal of

Event Group 14

Electr: IO Connection

Byte

1

32

Out Of

Specification (S)

C1.5.14

52018

52018

52018

52018

(0xCB32)

Status Signal of

Event Group 13

Proc: Signal Search

Byte

1

128

Failure (F)

C1.5.8

52019

52019

52019

52019

(0xCB33)

Status Signal of

Event Group 12

Proc: 2 Phase Flow

Byte

1

32

Out Of

Specification (S)

C1.5.10

52020

52020

52020

52020

(0xCB34)

Status Signal of

Event Group 11

Proc: Signal Low

Byte

1

32

Out Of

Specification (S)

C1.5.7

52021

52021

52021

52021

(0xCB35)

Status Signal of

Event Group 10

Config: Totaliser

Byte

1

32

Out Of

Specification (S)

C1.5.12

52022

52022

52022

52022

(0xCB36)

Status Signal of

Event Group 9

Proc: System Control

Byte

1

1

Information (I)

C1.5.11

52023

52023

52023

52023

(0xCB37)

Status Signal of

Event Group 8

Electr: Power Failure

Byte

1

32

Out Of

Specification (S)

C1.5.13