1 installation, 2 operating – KROHNE UFC 030 PROFIBUS PA User Manual

Page 11

background image

Supplementary documentation UFC030 with PROFIBUS-PA

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5

D-47058 Duisburg

11/17

Tel.: 0203-301 309

Fax: 0203-301389 · e-mail: [email protected]

9

Device Description for the SIMATIC Process Device Manager (PDM)

9.1 Installation

If the UFC 030 Device Description is not already installed on the PDM System a so called Device Install is needed
(available on floppy disk from KROHNE or as download from KROHNE internet page).
For installing the DD with the Device Install refer to the “PDM Manual” section ”Utilities” / “Device Install". Please read
also the “readme.txt”, which is contained in the Device Install.

9.2 Operating

Refer to the UFC 030 Menu Tree PDM (Attachment A).
Due to PROFIBUS and PDM requirements and conventions the UFC 030 operation differs from operation via local
keypad and the following peculiarities should be kept in mind:.

The online help of each parameter contains its function number as a reference to the device’s local display and
the “Installation and Operating Instructions”.

If the device is operated via its local keypad no write operation can be performed via the PROFIBUS interface at
the same time. Please check in case the flag ’Device is controlled via its keypad’ in ‘View / Details / Signal
Converter State’.

There are several complex dependencies between the parameters of the UFC 030. These dependencies can’t
be handled correctly to the full extent in the online dialogs of the PDM parameter table. Therefore it is
recommendable to switch these dialogs for the parameter table off. (See menu ‘Options / Customize / Table /
online dialog in the table available’).

In order to find out whether the setting of the device is still the same as the parameter set stored in PDM
compare the ‘Static Revision No.’ of the respective PROFIBUS Block. (The current Static Revision No. is
displayed on the window ‘View / Device Status / ’).