The transducer should be mounted preferably without socket,

flush with the vessel top.
If the reflective properties of the medium are good, you can

mount OPTISOUND 3040 C on a socket piece. The socket

end should be smooth and burr-free, if possible also rounded.

Carry out a false echo storage.

In liquids, direct the sensor as perpendicular as possible to the

product surface to achieve optimum measurement results.

Fig. 10: Orientation in liquids

To optimally align the sensor to solid products, a swivelling

holder can be implemented.

The ultrasonic sensor should be installed at a location where

no installations cross the ultrasonic beam.
Vessel installations such as for example, ladders, limit

switches, heating spirals, struts etc. can cause false echoes

superimposed on the useful echo. Make sure when planning

your measuring site that the ultrasonic signals have "free

access" to the measured product.
If there are existing vessel installations, a false echo storage

should be carried out during setup.
If large vessel installations such as struts or supports cause

false echoes, these can be attenuated through supplementary

measures. Small, inclined sheet metal or plastic baffles above

the installations scatter the ultrasonic signals and avoid direct

false echoes.

Socket

Sensor orientation

Vessel installations

18

OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire