beautypg.com

3 mounting information – KROHNE OPTISOUND 3040 C 4wire EN User Manual

Page 16

background image

1 Loosen the hexagon nut (3) on the transducer cable
2 Insert the transducer tube from below into the mounting

opening G1A

3 Fasten (SW 46) the hexagon nut (3)
4 Remove the plug from below out of the connection cylinder

and plug it into the socket of the transducer tube

5 Plug the connection cylinder to the transducer tube. Do not

squeeze any cables. The cylinder is in the correct position,

if the lower notch (2) of the transducer tube is no longer

visible

6 Tighten the screws (4) on the cylinder moderately with a

hexagon spanner (size 4)

7 Rotate the connection cylinder in such a way that the cable

entry points downwards (moisture can drain off). Fasten

the cylinder with screws (4); torque max. 5 Nm

8 Insert the plug at the end of the transducer cable into the

socket on the remote electronics

1

2

3

4

Fig. 7: Assembling – version D

1

Groove for locking the connection cylinder

2

Marking notch

3

Hexagon nut SW 46

4

Screws of connection cylinder (hexagon spanner - size 4)

4.3 Mounting information

When mounting OPTISOUND 3040 C, keep a distance of at

least 500 mm to the vessel wall. If the sensor is installed in the

center of concave or arched vessel tops, multiple echoes can

arise. These can, however, be faded out by an appropriate

adjustment (see chapter "Setup").

Installation position

16

OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire

Mounting

30515

-EN
-050914