3 mounting information – KROHNE OPTISOUND 3040 C 4wire EN User Manual
Page 16
1 Loosen the hexagon nut (3) on the transducer cable
2 Insert the transducer tube from below into the mounting
opening G1A
3 Fasten (SW 46) the hexagon nut (3)
4 Remove the plug from below out of the connection cylinder
and plug it into the socket of the transducer tube
5 Plug the connection cylinder to the transducer tube. Do not
squeeze any cables. The cylinder is in the correct position,
if the lower notch (2) of the transducer tube is no longer
visible
6 Tighten the screws (4) on the cylinder moderately with a
hexagon spanner (size 4)
7 Rotate the connection cylinder in such a way that the cable
entry points downwards (moisture can drain off). Fasten
the cylinder with screws (4); torque max. 5 Nm
8 Insert the plug at the end of the transducer cable into the
socket on the remote electronics
1
2
3
4
Fig. 7: Assembling – version D
1
Groove for locking the connection cylinder
2
Marking notch
3
Hexagon nut SW 46
4
Screws of connection cylinder (hexagon spanner - size 4)
4.3 Mounting information
When mounting OPTISOUND 3040 C, keep a distance of at
least 500 mm to the vessel wall. If the sensor is installed in the
center of concave or arched vessel tops, multiple echoes can
arise. These can, however, be faded out by an appropriate
adjustment (see chapter "Setup").
Installation position
16
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire