KROHNE IFC 090F Converter EEx-ATEX EN User Manual

Page 8

background image

ALTOFLUX IFC 090 F-EEx and ALTOFLUX IFC 090 F / i-EEx

8

Cable B
Power supply cable: The cable parameters must be in accordance with the regulations of the EN
60079-14 "Electrical installations in hazardous locations" or an equivalent national standard.

The PE terminal must be connected to the protective ground conductor of the mains supply.

Rated voltage

≥ 500 V

Cross-sectional area of core

1.5 to 2.5 mm

2

Examples H07...-.,

H05...-.

Cable C

1

2
3
4
5
6
7
8

3 3

7

1

6

4

Type DS blue
Intrinsical safe, with double shielding

1 Stranded drain wire,
1st shield, 1.5 mm

2

2 Insulation
3 Stranded wire, 0.5 mm

2

4 Special foil, 1st shield
5 Insulation
6 Mu-metal foil, 2nd shield
7 Stranded drain wire,
2nd shield, 0.5 mm

2

8 Outer sheath
(flame-retardant)

Cable constants (typical
values at Ta = 20°C)

C’3/3 60 pF/m (1 kHz)
C’3/4 110 pF/m (1 kHz)
C’4/6 290 pF/m (1 kHz)

L’3/3 0.85 µH/m (1 kHz)
L’3/4 0.60 µH/m (1 kHz)

R’3

37 m

Ω/m

R’4+1 12 m

Ω/m


Cable D
Intrinsical safe, with single shielding. Heat-resistant conform to VDE 0165/02.91.

Properties
Continuous service temperature

≥ 120°C

Test voltage

≥ 500 V

Capacitance:

≤ 200 pF/m

≤ 200 pF/m

Inductance:

≤ 1µH/m

Cable length

≤ 5 m

Single-wire-Ø:

≥ 0.1 mm

Cross-sectional area of core

0.5 to 1.5 mm

2

Sheath

light-blue or in other way color-coded as intrinsical safe,
flame-retardant.

Example

Silicone rubber insulated, shielded control cable.


Cable E
Non-intrinsical safe, 2-core without shielding. Heat-resistant conform to VDE 0165/02.91.

Properties
Continuous service temperature

≥ 120°C

Test voltage

≥ 500 V

Cross-sectional area of core

1.5 mm

2


Bonding conductor
Cross-sectional area

Max. 4 mm

2