beautypg.com

KROHNE IFC 090F Converter EEx-ATEX EN User Manual

Page 17

background image

ALTOFLUX IFC 090 F-EEx and ALTOFLUX IFC 090 F / i-EEx

17

Connection diagrams 1 to 4 of the intrinsically safe signal in-/outputs

1

Current output I

active

2

Current output I

passive

Version: Ex-i3

Versions:

Ex-i1, Ex-i2, Ex-i7

I = 4 - 20 mA

U

ext

= 8.1 - 30 V

R

i

= 350

I = 4 - 20 mA

R

i

≤ (U

ext

- 8) / 0.022

IFC 090 i-EEx

IFC 090 i-EEx

hazardous area

hazardous area

safe area or

safe area or

hazardous area (

*

)

hazardous area (

*

)

3

Pulse output P

active

4

Pulse output P

passive

Version: Ex-i5

Versions:

Ex-i1, Ex-i4, Ex-i6, Ex-i8

U

int

= 20 V DC

U

ext

= 6 - 30 V DC

R

int

= 260

I

max

≤ 110 mA

U

L

= 20×R

L

/ (260+R

L

)

IFC 090 i-EEx

IFC 090 i-EEx

hazardous area

hazardous area

safe area or

safe area or

hazardous area (

*

)

hazardous area (

*

)

passive counter

passive counter with
external supply

(

*

) Important note:

Only if the measuring devices are also explosion protected