Current output

Output mode

4 … 20 mA

20 … 4 mA

Failure mode

1)

Hold value

20.5 mA

22.0 mA

<3.6 mA

Min. current

2)

3.8 mA

4 mA

The values in bolt font represent the data of the factory

setting.
In HART multidrop mode, the current is constantly 4 mA.

This value does not change even in case of failure.

Current output

Output mode 4-20 mA
Failure mode: 22mA
Min-current 3.8mA

HART offers standard and multidrop mode

3)

. In multi-

drop mode up to 15 sensors can be operated on one

two-wire cable.
In this menu item you determine the HART mode and

enter the address with multidrop.

HART mode

standard
Address 0

1)

Value of the current output in case of failure, e.g. if no valid

measured value is delivered.

2)

The current never falls below this value during operation.

3)

In multidrop mode, the 4 … 20 mA signal of the HART sensor is

switched off. The sensor consumes a constant current of 4 mA.

The meas. signal is only transmitted as digital HART signal.

HART mode

Indicating/adjustment module for OPTISOUND sensors