KROHNE OPTISOUND 3000 Series EN User Manual

Page 15

background image

To damp process-dependent measured value fluctua-

tions, you have to set an integration time of 0 … 999 s in

this menu item.

Damping

In this menu item you select the linearization curve:

l

linear

l

Cylindrical tank

l

Spherical tank

l

User programmable

User programmable means: Switching on a linearization

curve programmed via PC and PACTware™
The linearization curve relates height and volume. It

takes the vessel geometry for the measured value

display and the current output into account.

Lineari-
zation
curve

linear

In the menu item "Sensor TAG" you edit a 12-digit

measurement loop character. The character set com-

prises:

l

Letters from A … Z

l

Numbers from 0 … 9

l

Special characters +, -, /, –

Sensor
TAG

Sensor

Min. and max. measured values are saved in the sensor.

The values are displayed in the menu item "Peak

values".

l

Min. and max. distance in m(d)

l

Min. and max. temperature

Damping

Linearization curve

Edit senor TAG

Peak values

Indicating/adjustment module for OPTISOUND sensors

15

Set up

30603

-EN

-050401