beautypg.com

Operation – KROHNE OPTIFLEX 1100C Quickstart EN User Manual

Page 17

background image

OPERATION

4

17

OPTIFLEX 1100 C

www.krohne.com

01/2012 - 4001226201 - QS OPTIFLEX 1100 R01 en

Procedure

Screen

Steps

Description

[>>>>] 3 times.

Default screen.

Enter configuration mode.

[>>>>] YES - to start the quick set-up
procedure, or [

] NO - to go back to the

menu.

[

] or [

] for the selection of the probe

type (COAXIAL or SINGLE CABLE).

[^

^

^

^] to confirm.

[>>>>] to change the probe length.

[>>>>] to change the position of the cursor.

[

] to decrease the value or [

] to

increase the value.

[^

^

^

^] to confirm.

Change this value if you have decreased the

length of the probe. The probe length for the

cable probe options includes the length of

the countweight.

[

] or [

] for the selection of the

measurement name (Distance, Level,
Conversion or Ullage Conv.).

[^

^

^

^] to confirm.

If "Level" or "Conversion" is set, the 0% limit

for the 4...20 mA scale is at the bottom of

the tank. If "Distance" or "Ullage Conv." is

set, the 0% limit is at the top of the tank.

[>>>>] to change Scale 4 mA.

[>>>>] to change the position of the cursor.

[

] to decrease the value or [

] to

increase the value.

[^

^

^

^] to confirm.

Use this step to give the 4 mA output setting

(0% limit) in the tank. Distance is measured

from the thread stop of the process

connection.

[>>>>] to change Scale 20 mA.

[>>>>] to change the position of the cursor.

[

] to decrease the value or [

] to

increase the value.

[^

^

^

^] to confirm.

Use this step to give the 20 mA output

setting (100% limit) in the tank. Distance is

measured from the thread stop of the

process connection.

After 8 seconds the Quick Setup is

completed.

[^

^

^

^] to confirm.

[

] or [

] for the selection of the save

option (STORE NO or STORE YES).

[^

^

^

^] to confirm.

Set to STORE YES to save and use the data.

Set to STORE NO to cancel the changes to

the device settings.