Installation – KROHNE OPTIFLEX 1100C Quickstart EN User Manual

Page 10

background image

2

INSTALLATION

10

OPTIFLEX 1100 C

www.krohne.com

01/2012 - 4001226201 - QS OPTIFLEX 1100 R01 en

• Pull the signal cable from the bottom of the last segment of tube. Apply 10 kgf / 22 lbf.
• Attach the screws for the signal cable to the probe end cap. Tighten with a 3 mm Allen wrench.

• Cut the signal cable 20 mm / 0.8¨ below the last segment of tube.

i

The device is prepared for installation on the tank.

If you decreased the probe length, you must enter the new probe length in the device
configuration menu (NOTE: the device must have the LCD display option or the HMI service tool).
For more data, refer to

Quick Setup

on page 16.

Make sure that the tension in the signal cable is correct

Figure 2-8: How to assemble the segmented coaxial probe: part 4

1 Coaxial probe: Signal cable
2 Coaxial probe: Probe end cap
3 2 HC M6×5 screws

Cut the signal cable to the correct length

Figure 2-9: How to assemble the segmented coaxial probe: part 5

c = 20 mm / 0.8¨
1 Coaxial probe: bottom of the last segment of tube
2 Coaxial probe: signal cable