8.2.3

Technical data of ESK II

Auxiliary power

12 (18 * ) to 30 V DC

Measurement signal

4.00 to 20.00 mA for 0 to 100 % flow value

>

20.8

mA

for

alarm

status

Auxiliary power influence <

0.1%

Dependency on external resistance

< 0.1%

Temperature

influence

<

5

μA / K

Max. external resistance / load

0 (250 * ) to 800 Ohms


* These values are to be observed as minimum values during HART

TM

communication.



9 Service

9.1 Contact

insert


Bring the contact pointers (1) together in the center

Loosen the locking screw (2) of the contact pointers

Slide the contact insert into the third rail until the semicircle (3)

encloses the pointer support.


The connecting terminals of the contact insert have a pluggable

design and can be removed in order to connect the lines.







9.2

Installing an ESK


Assembly is based on the plug-in technique.

Insert the push-in lugs of the ESK under the

two studs of the baseplate (1).

Using slight pressure, press the ESK on to

the spring bolt (2) until it locks home and is securely

fastened.