beautypg.com

KROHNE DA Flap-type EN User Manual

Page 13

background image

Definition of Min1 and Min2 /

Max1 and Max2








Min1


Min2














Max1


Max2










8.1.4

Technical data of limit switches

SC3,5-N0-Y

SJ3,5-SN

SJ3,5-S1N

SB3,5-E2

2-wire

2-wire

2-wire

3-wire

NAMUR

NAMUR

NAMUR

Switching element function

NC contact

NC contact

NO contact

NO contact PNP

Nominal voltage U0

8 V

8V

8V

10 to 30 V

Power consumption:

Pointer vane not detected

≥ 3 mA

≥ 3 mA

≤ 1 mA

≤ 0.3 V

Pointer vane detected

≤ 1 mA

≤ 1 mA

≥ 3 mA

Ub - 3 V

Continuous current

-

-

-

max. 100 mA

No-load current I0

-

-

-

≤ 15 mA


An isolating switching amplifier, e.g. Pepperl + Fuchs Series KF .. -SR2 ..., is required in order to

operate

the

SC3,5-N0-Y

limit switch (refer to the chapter on the spare part list).


SJ3,5-SN

and SJ3,5-S1N limit switches safety-oriented are connected to a safety-oriented isolating

switching amplifier, e.g. Pepperl + Fuchs K… –SH- ... (large S on the front)

current

consumption

with

the

shown

pointer

position

SC3,5-N0

≤1 mA



SJ3,5-S1N

≤1 mA

current

consumption

with

the

shown

pointer

position

SJ3,5-S1N

≥3 mA



SC3,5-N0

≥3 mA