ELECTRICAL INSTALLATION

3

Rear of the I/O rack


Items marked with connections to the UFP-V Flow Processor are pre-wired. It concerns power
inlet and the I/O communication. Connect these connectors in the prescribed way to the flow
processor. In the table below the signals and their respective connections are listed preset on
the terminals on the terminals at the back side of the I/O rack.

Terminal No.

Function / Description

+

-

If applicable pos. or neg. signal level

1 TX-



Modbus RS422/RS485 data comm.

2 TX+
3 RX-
4 RX+
5 Return
6 NC
7

8

4…20 mA current output (e.g. actual flow)

9

10

Power for pulse outputs if passive output must be activated externally

11

12

Pulse output 1

13

14

Pulse output 2

15 16

Reset

totalizers

17 18

Reset

alarms

19 20

Start

calibration

For factory use only

21 22

Stop

calibration

23

24

Failure signal output

25

26

Warning signal output

27

28

Forward flow direction > low flow cut-off forward

29 30

Reverse

flow

direction

> low flow cut-off reverse

31 A

RS485 flow data from UFC-V to UFP-V

32 B
33 Return

PE

Safety grounding

Mains 115 / 230 VAC - 50-60Hz

PE
N

Neutral

N
L

Phase

L

For the connections to PLC’s and other equipment used in the installation, shielded cables shall
be used and the shielding shall be connected to the ground rail using the provided shield
grounding clamps. These shields are part of the CE conformity. Not respecting these rules may
lead to EMC problems. If grounding is prohibited according to other rules or regulations a
capacitor shall be used to get a HF bounding of the shields (capacitor not included with supply).


The electrical safety grounding shall be provided on the green yellow colored connection
terminal, marked with PE. Local installation regulations and general practice shall be respected