ELECTRICAL INSTALLATION

3

3.8 Connecting the outputs of the UFP-V I/O-rack

The I/O signals are wired to the connection terminal. This terminal is client specified, therefore
only an example can be given.

Connector X1 Flow Computer UFP-V I/O-rack

This is an example, position numbers may differ, see connection diagram supplied with
flowmeter.

Connection parameters per type for UFP card MP103:

Connection parameter

Card and connector

Limitations

Digital inputs

Mp103 card
DB9 Connector 1

TTL compatible
Umax =12 V
Imin =1mA
Imax =10mA

Relay outputs

MP103 card
DB9 Connector 2

Switchable:
Umax

=150Vdc, 125Vac

Imax =0.2A

Current output

MP103 card
DB9 Connector 3

Active(0..22mA): R load < 500 Ohm
Passive : Uext= 8.1…30V

R load = (Uext- 8V) / 22mA

I = 0..22mA

Pulse outputs

MP103 card
DB9 Connector 3

Selectable by jumper setting on MP103 card
24V

: Imax-out = 10mA, Ri=2k4

12V

: Imax-out = 5mA , Ri=2k4

Open Collector: Umin

= 1V, Imax =10mA

Pulse Power

MP103 card
DB9 Connector 3

Only for use in Internal Pulse circuit
(external 2k2 resistors to activate passive
pulse outputs)

Frequency inputs

MP103 card
DB9 Connector 6

Open Collector: Umax =5V, Isink = 5mA
Usually connected through barrier