beautypg.com

1 general information, Point-to-point analog/digital mode – KROHNE IFC 300 Converter HART 0201 User Manual

Page 3

background image

Supplementary Handbook IFC 300 HART, FC375, AMS, PDM, DTM

1 General Information

The IFC 300 is a “four-wire” transmitter with 4...20mA current output and HART

® capability. Dependent on

jumper setting and/or wiring the current output can operate as active or passive output.

General characteristics of the IFC 300 HART

® interface:

• Multidrop Mode is supported

• Burst Mode is not supported

Electrical connection: Refer to section “Electrical connection: outputs and inputs” of the following manual:

• “Handbook IFC 300 signal converter” (KROHNE)


There are two ways of using the HART

® communication:


a) As a point-to-point connection between the IFC 300 and the HART master equipment. The instrument's
current output may be active or passive.

Point-to-Point Analog/Digital Mode

4

20

mA

4...20 mA

Power
Supply

250 Ω

HART

Modem

HART

Analog

Primary Master

Secondary Master

IFC 300

Addr. 0

For slaves with
passive current
output (2 wire)

Terminal A (C)

Terminal A- (C-)


HART_Suppl_IFC300_V0201.DOC

04/2007

3/23