beautypg.com

Figure 2. power rating vs. temperature, Operation, Power rating vs. temperature – KEPCO RKW 600W Series Operator Manual User Manual

Page 7: Mounting positions for the rkw 600w power supply, Re 2

background image

RKW 600W 060110

5

FIGURE 2. POWER RATING VS. TEMPERATURE

FIGURE 3. MOUNTING POSITIONS FOR THE RKW 600W POWER SUPPLY

3.

OPERATION

Figure 4 shows the location of all operating controls and input/output terminals followed by an
explanation of each. The unit is shipped with shorting links installed connecting the following ter-
minals: +RC to –RC and REF to RV. A local sensing cable is also installed, connecting +DC
Output with +S and –DC Output with –S for local sensing.

NOTES:

1. +S and –S MUST be properly connected for the unit to operate. For local

sensing, leave local sense cable in place (refer to PAR. 5.1). For remote
sensing (at the load), refer to PAR. 5.2.

2. If remote ON/OFF is not being used, ±RC terminals must be connected

(use shorting link supplied) for unit to operate.