beautypg.com

Description, Options, Table 1. model parameters – KEPCO KLP Series Quick Start Guide, P/N 228-1773 User Manual

Page 2: Unpacking, Equipment supplied, Table 2. equipment supplied, Options unpacking equipment supplied, See t able 2

background image

2

228-1773 REV 1

091713

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102

http://www.kepcopower.com email: [email protected]

DESCRIPTION.

The KLP Power Supply Series are universal input, automatic crossover, 1200-watt

constant power, voltage/current stabilizers with a full rectangular output characteristic. There are seven
standard models (also referred to as -1200) and seven E -Series models (formerly referred to as -1.2K)
(see Table 1). The standard models are GPIB and RS 232 compatible; the E-Series models are GPIB
and LAN compatible; all models allow remote analog programming. For each model a multitude of virtual
models can be configured. The “rated voltage, maximum current at rated voltage” and “rated current and
maximum voltage at rated current” parameters define the virtual models available within the limit of 1200
Watts of output power.

OPTIONS.

The Rapid Output Discharge Circuit (RODC) option (suffix R) is available on all KLP mod-

els. This circuit rapidly discharges the output capacitance, thus significantly reducing response time to
reductions in output voltage (see KLP User Manual for details).

UNPACKING.

This instrument has been thoroughly inspected and tested prior to packing and is

ready for operation. After careful unpacking, inspect for shipping damage before attempting to operate.
Perform the PRELIMINARY OPERATIONAL CHECK. If any indication of damage is found, file an imme-
diate claim with the responsible transport service.

EQUIPMENT SUPPLIED

.

See Table 2.

TABLE 1. MODEL PARAMETERS

Model number

Rated

Voltage

Range

(1)

Maximum

current for

rated voltage

Minimum

programmable

current

Rated

Current

Range

(1)

Maximum

voltage for

rated current

Ripple

and

noise
p-p

(2)

Efficiency

@115 Va-c

KLP 10-150

(3)

0-10V

120A@10V

1.9A

0-150A

8V@150A

60 mV

80%

KLP 20-120

(3)

0-20V

60A@20V

1.5A

0-120A

10V@120A

60 mV

82%

KLP 36-60

(3)

0-36V

33.3A@36V

0.8A

0-60A

20V@60A

60 mV

83%

KLP 75-33

(3)

0-75V

16A@75V

0.4A

0-33.3A

[email protected]

60 mV

84%

KLP 150-16

(3)

0-150V

8A@150V

0.2A

0-16A

75V@16A

125 mV

86%

KLP 300-8

(3)

0-300V

4A@300V

0.1A

0-8A

150V@8A

150 mV

87%

KLP 600-4

(3)

0-600V

2A@600V

0.05A

0-4A

300V@4A

150 mV

88%

(1) The maximum current and voltage are constrained by the 1200 watt power limitation.
(2) Bandwidth: 20MHz; low frequency ripple may be higher at loads less than 30 Watts.
(3) Specifications listed apply to both standard (-1200) and E-Series (suffix E) models.

TABLE 2. EQUIPMENT SUPPLIED

ITEM

PART NUMBER

QUANTITY

Jumper (24 AWG or larger bus wire) for local sensing connections

172-0638

2

Analog I/O port mating connector

142-0528

1

Nut, 1/4-20, with captive lockwasher (on output studs of 10V, 20V and 36V models only)

102-0175

2

Quick Start Guide *

228-1773

1

* User Manual and Developer’s Guide are available as free downloads from:
www.kepcopower.com/support/opmanls.htm#klp
Drivers are available as free downloads from
www.kepcopower.com/drivers/drivers-dl3.htm#klp