OUTPUT CHARACTERISTICS:
SOURCE EFFECT:
±1% @ 115V a-c and 230V a-c,
±10%, rated load
LOAD EFFECT:
KDN 24-5:
±1% max. from 0 to 5A
KDN 24-10: ±2% max. from 0 to 10A
KDN 24-20: ±1% max. from 12A down to 4A and from
12A up to 20A
SETTING TOLERANCE:
±2%
TRANSIENT RECOVERY:
Excursion produced by step
load change from 20% to 100% and 100% to 20@:
KDN 24-5:
100mV max., 1mS max. recovery
KDN 24-10: 200mV max., 1mS max. recovery
KDN 24-20: 1V max., 1mS max. recovery
START UP TIME:
KDN 24-5:
1.7S typ @ 115V a-c, <1S @ 230V a-c
KDN 24-10: 1.9S typ @ 115V a-c, <1S @ 230V a-c
KDN 24-20: 1.8S typ @ 115V a-c, <1S @ 230V a-c
HOLD UP TIME:
115V a-c input voltage, rated load: >20
milliseconds typical (measured from end of last charging
pulse to when output drops to 95%)
EFFICIENCY:
KDN 24-5:
87% (typ.)
KDN 24-10: 85% (typ.)
KDN 24-20: 85% (typ.)
POWER OK INDICATOR:
OFF when unit in overcurrent
protection, a-c input is off, and as follows:
KDN 24-5:
Output voltage <15V d-c
KDN 24-10: Output voltage <20.5V to 23.5V d-c
KDN 24-20: Output voltage <11 to 13V d-c
ENVIRONMENTAL CHARACTERISTICS
OPERATING TEMPERATURE:
perature derating. Do not allow the power supply vents to
become dust covered because that will decrease the cooling
efficiency of the unit and cause insulation to deteriorate.
KDN 24-5: -10°C to +70°C
KDN 24-10: 0°C to +70°C
KDN 24-20: -10°C to +70°C; start up: -10°C,
@ nominal input voltage only.
STORAGE TEMPERATURE:
-40°C to + 85°C.
COOLING:
Natural convection.
ALTITUDE:
0 to 10,000 feet.
GENERAL CHARACTERISTICS
MTBF:
Per MIL HDBK 217F (GB), 230V a-c line, 40°C:
KDN 24-5: 260,000h @ 24V d-c, 5A
KDN 24-10: 425,000h @ 24V d-c, 10A
KDN 24-20: 310,000h @ 24V d-c, 20A
OVERVOLTAGE PROTECTION:
When output voltage
exceeds OVP value (see Table 1) output is cut off to protect
the load. To reset, briefly remove, then restore, a-c input
power.
OVERCURRENT PROTECTION:
Power supply enters
hiccup mode if short circuit or overcurrent condition exists;
recovery is automatic when cause is removed.
EMC - EMISSIONS:
Designed to meet:
Radiated Noise 30MHZ to 1GHz:
FCC docket 20780 Class B, EN55022-B
Conducted Noise 0.15MHz to 30MHz:
FCC Class B, EN55022-B
Input Harmonics (on AC Mains) 0 to 2KHz:
EN 61000-3-2 Class D
EMC - IMMUNITY:
ESD (6KV contact discharge, 8KV air discharge):
EN 61000-4-2
Radiated Field:
EN 61000-4-3 (10mV, Criteria B)
Electrical Fast Transient/Burst (EFT):
EN 61000-4-4 (2KV)
Surge:
EN 61000-4-5 (4KV)
Conducted Noise:
EN 61000-4-6 (Criteria A)
Power Frequency Magnetic Field:
EN 61000-4-8 (Criteria A)
Voltage Dips, Short Interruptions, Voltage Variation:
EN 61000-4-11
SAFETY:
All units are UL 508 listed and are designed to
meet UL 1950, CSA 22.2 No. 950-M90 and EN 60950. KDN
units are CE marked per the Low Voltage Directive (LVD), EN
60950.
ORIENTATION:
WEIGHT:
KDN 24-5:
1.61 lbs (730g)
KDN 24-10: 2.43 lbs (1100g)
KDN 24-20: 4.36 lbs (1980g)
WARRANTY:
One year.