OUTPUT CHARACTERISTICS:

SOURCE EFFECT:

±1% @ 115V a-c and 230V a-c,

±10%, rated load

LOAD EFFECT:

KDN 24-5:

±1% max. from 0 to 5A

KDN 24-10: ±2% max. from 0 to 10A
KDN 24-20: ±1% max. from 12A down to 4A and from
12A up to 20A

SETTING TOLERANCE:

±2%

TRANSIENT RECOVERY:

Excursion produced by step

load change from 20% to 100% and 100% to 20@:
KDN 24-5:

100mV max., 1mS max. recovery

KDN 24-10: 200mV max., 1mS max. recovery
KDN 24-20: 1V max., 1mS max. recovery

START UP TIME:

KDN 24-5:

1.7S typ @ 115V a-c, <1S @ 230V a-c

KDN 24-10: 1.9S typ @ 115V a-c, <1S @ 230V a-c
KDN 24-20: 1.8S typ @ 115V a-c, <1S @ 230V a-c

HOLD UP TIME:

115V a-c input voltage, rated load: >20

milliseconds typical (measured from end of last charging
pulse to when output drops to 95%)

EFFICIENCY:

KDN 24-5:

87% (typ.)

KDN 24-10: 85% (typ.)
KDN 24-20: 85% (typ.)

POWER OK INDICATOR:

OFF when unit in overcurrent

protection, a-c input is off, and as follows:
KDN 24-5:

Output voltage <15V d-c

KDN 24-10: Output voltage <20.5V to 23.5V d-c
KDN 24-20: Output voltage <11 to 13V d-c

ENVIRONMENTAL CHARACTERISTICS

OPERATING TEMPERATURE:

See Figure 2 for tem-

perature derating. Do not allow the power supply vents to
become dust covered because that will decrease the cooling
efficiency of the unit and cause insulation to deteriorate.

KDN 24-5: -10°C to +70°C
KDN 24-10: 0°C to +70°C
KDN 24-20: -10°C to +70°C; start up: -10°C,

@ nominal input voltage only.

STORAGE TEMPERATURE:

-40°C to + 85°C.

COOLING:

Natural convection.

ALTITUDE:

0 to 10,000 feet.

GENERAL CHARACTERISTICS

MTBF:

Per MIL HDBK 217F (GB), 230V a-c line, 40°C:

KDN 24-5: 260,000h @ 24V d-c, 5A
KDN 24-10: 425,000h @ 24V d-c, 10A
KDN 24-20: 310,000h @ 24V d-c, 20A

OVERVOLTAGE PROTECTION:

When output voltage

exceeds OVP value (see Table 1) output is cut off to protect
the load. To reset, briefly remove, then restore, a-c input
power.

OVERCURRENT PROTECTION:

Power supply enters

hiccup mode if short circuit or overcurrent condition exists;
recovery is automatic when cause is removed.

EMC - EMISSIONS:

Designed to meet:

Radiated Noise 30MHZ to 1GHz:

FCC docket 20780 Class B, EN55022-B

Conducted Noise 0.15MHz to 30MHz:

FCC Class B, EN55022-B

Input Harmonics (on AC Mains) 0 to 2KHz:

EN 61000-3-2 Class D

EMC - IMMUNITY:

ESD (6KV contact discharge, 8KV air discharge):

EN 61000-4-2

Radiated Field:

EN 61000-4-3 (10mV, Criteria B)

Electrical Fast Transient/Burst (EFT):

EN 61000-4-4 (2KV)

Surge:

EN 61000-4-5 (4KV)

Conducted Noise:

EN 61000-4-6 (Criteria A)

Power Frequency Magnetic Field:

EN 61000-4-8 (Criteria A)

Voltage Dips, Short Interruptions, Voltage Variation:

EN 61000-4-11

SAFETY:

All units are UL 508 listed and are designed to

meet UL 1950, CSA 22.2 No. 950-M90 and EN 60950. KDN
units are CE marked per the Low Voltage Directive (LVD), EN
60950.

ORIENTATION:

Vertical only (see Figure 1)

WEIGHT:

KDN 24-5:

1.61 lbs (730g)

KDN 24-10: 2.43 lbs (1100g)
KDN 24-20: 4.36 lbs (1980g)

WARRANTY:

One year.