2. Operating in manual mode
When the VisorALARM PLUS 2U receiver has no Automation Software connected or the Automation
Software has failed, the receiver must be operated in manual mode.
In manual mode signals must be visualized and acknowledged from the receiver through the receiver
LCD and keypad.
When a signal arrives at the receiver in manual mode, the LCD shows a status line as follows:
PRIMARY VisorALARM
1 Signal pending
If you are not logged into the VisorALARM PLUS 2U receiver when events are received pressing the
ACK key for the first time will display the highest priority event and silence the receiver piezo. If the
ACK key is pressed a second time you will be prompted for a password. Once you have entered the
password, the highest priority event is displayed once more and the piezo sounder buzzes again.
Repeatedly pressing the ACK key will now display and acknowledge subsequent events.
Subsequently the signal information is shown in the display with the next format:
16:33:23 00001234 »
E110 01 001 Fire
The LCD shows the following information:
hh:mm:ss: The hour, minutes and seconds of the alarm in a 24 hours format
aaaaaaaa: The eight digit account code
Q: Qualificator, E= New event or opening; R=Restoration or closing; P=Status report.
XYZ: Event code
GG: Number or group or partition.
CCC: Zone number or user identifier.
TTTTTTT: Textual description for the event code. This contemplates the following values:
Event Code
TTTTTTT
10x
Medical
11x
Fire
12x
Panic
13x
Burglar
14x, …, 1Fx
Alarm
2xx
Superv
3xx
Trouble
4xx
Opn/Cls
hh:mm:ss aaaaaaaa »
QXYZ GG CCC TTTTTTTTT