beautypg.com

Figure 2-4: surface mounting – Fire-Lite LED-10 Series Remote Fire Annunciator User Manual

Page 15

background image

15

Document 50400 Rev B 10/27/97 P/N 50400:B

Surface Mount Backbox

Remove the plug-in terminal blocks from the LED-10 Series circuit board. Connect the
EIA-485 and power wiring into the terminal block positions illustrated in Figures 3-1 and
3-3. Plug the terminal blocks back into the TB1 and TB2 connectors on the back of the
annunciator circuit board.

Set DIP switches SW1 and SW2 for the desired options (refer to switch settings in
Figures 1-3, 1-4 and Table 1-1).

Mount the LED-10 Series to a three-gang electrical box using the four mounting holes
on the annunciator flange and the four screws provided for this purpose. Replace the
trim ring and secure with the two screws which were previously removed.

Do not

overtighten.

Figure 2-4: Surface Mounting

LED-10 Series flange

Mounting Holes (4)

flange

Three-gang electrical box
(Fire•Lite P/N SBB-3 or equivalent
with 2.75" minimum depth).

EIA-485 and power wiring

LED-10 Series