Fire-Lite M302(A) Two-Wire Conventional Detector Monitor Modules User Manual
Page 2

TESTING
The M302(A) monitor module can be tested with a test magnet available from Fire-Lite (M02-04-00, see Figure 1). The magnet
test checks the module’s electronics and connections to the control panel. Interfaced two-wire detectors must be tested inde-
pendently. Test two-wire detectors per manufacturer’s installation instructions.
M302(A) MONITOR MODULE WIRING DIAGRAMS
Figure 3. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE B
Figure 4. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE D
F400-09-00
2
I56-631-06
1 (–)
2 (+)
MODULE
(+)
(–)
(–) 9
(+) 8
(+) 7
(–) 6
M302(A)
MONITOR
FROM PANEL OR
(+)
(–)
CONNECT MODULES TO LISTED
COMPATIBLE ADDRESSABLE FIRE-LITE
CONTROL PANELS ONLY.
32 VDC MAX.
TO NEXT
(+)
(–)
DEVICE
LISTED BATTERY BACK-UP, SWITCHED
DC POWER SUPPLY.
SEE REQUIREMENTS ON PAGE 4.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO ENSURE SUPERVISION OF CONNECTIONS.
INSTALL MODULE PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
IDC INSTALLATION WIRING MUST NOT EXCEED
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
POWER TO THE MONITOR MODULE
MUST BE EXTERNALLY SWITCHED TO
CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
OPTIONAL BRANCH CIRCUIT
2-WIRE CONVENTIONAL DETECTOR
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE.
+
–
+
–
RESISTOR
(INCLUDED)
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
3 (–)
4 (+)
(–)
(+)
5
UL LISTED POWER SUPPLY - SEE FIGURE 5.
PREVIOUS DEVICE
RESET THE DETECTORS. A C300
TO NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
COMMUNICATION LINE
POWER LIMITED: 90ma MAX; 28 VDC MAX
25 OHMS, 12 - 18 AWG.
3.9K EOL
REFER TO FIRE-LITE PRODUCT MANUAL
FOR WIRE SPECIFICATIONS.
ALL WIRING SHOWN IS SUPERVISED.
A78-2394-631
(SHIELD)
(SHIELD)
TERMINAL WIRING MUST BE POWER LIMITED.
1 (-)
2 (+)
MODULE
(+)
(-)
(-) 9
(+) 8
(+) 7
(-) 6
M302(A)
MONITOR
FROM PANEL OR
(+)
(-)
CONNECT MODULES TO LISTED
COMPATIBLE ADDRESSABLE FIRE-LITE
CONTROL PANELS ONLY.
32 VDC MAX.
REFER TO FIRE-LITE PRODUCT
MANUAL FOR WIRE SPECIFICATIONS
TO NEXT
(+)
(-)
DEVICE
LISTED BATTERY BACK-UP,
SWITCHED DC POWER SUPPLY.
SEE REQUIREMENTS ON PAGE 4.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO ENSURE SUPERVISION OF CONNECTIONS.
INSTALL DETECTORS PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
POWER TO THE MONITOR MODULE
MUST BE EXTERNALLY SWITCHED TO
CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE.
+
-
+
-
OPTIONAL BRANCH CIRCUIT
(-)
(+)
3 (-)
4 (+)
5
UL-LISTED POWER SUPPLY - SEE FIGURE 5.
PREVIOUS DEVICE
RESET THE DETECTORS. A C300
TO NEXT MONITOR MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
COMMUNICATION LINE
IDC INSTALLATION WIRING MUST NOT EXCEED
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
2-WIRE CONVENTIONAL DETECTOR
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE D
POWER LIMITED: 90ma MAX; 28 VDC MAX
25 OHMS, 12 - 18 AWG.
3.9K EOL RESISTOR
REQUIRED AT TERMINALS
8 & 9 (INCLUDED)
ALL WIRING SHOWN IS SUPERVISED.
A78-2395-631
(SHIELD)
(SHIELD)
TERMINAL WIRING MUST BE POWER LIMITED.