Fire-Lite M302(A) Two-Wire Conventional Detector Monitor Modules User Manual

Fire-Lite Equipment

background image

INSTALLATION INSTRUCTIONS FOR M302(A)

TWO-WIRE CONVENTIONAL DETECTOR MONITOR MODULE

This information is included with the modules as a quick reference installation guide. Refer to the appropriate Fire-Lite product
manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the
modules.

GENERAL DESCRIPTION
The M302(A) monitor module allows addressable panels to interface and moni-
tor two-wire conventional smoke detectors. All two-wire detectors being moni-
tored must be UL compatible with the module.

The module is addressed through the communication line (SLC) of address-
able systems. When the module is interrogated, it transmits the status of one
zone of two-wire detectors to an addressable control panel. Status conditions
are reported as NORMAL, OPEN, or ALARM. The monitor module supervises
the zone of detectors and the connection of a power source.

Two rotary decade switches allow setting module addresses from 00–99. A
status LED indicator is provided and is controlled by code command from the
control panel. The module provides a magnetically activated test switch for
testing the module’s electronics and connections to the control panel (see Fig-

STATUS LED

ROTARY DECADE
ADDRESS SWITCHES

MAGNET TEST
POSITION

2

7

0

1

3

4

5

6

8

9

2

7

0

1

3

4

5

6

8

9

A78-2318-00

FIGURE 1.

MODULE CONTROLS AND INDICATORS

ure 1).

COMPATIBILITY REQUIREMENTS
To insure proper operation, this module shall be connected to compatible Fire-Lite addressable control panels only.

Conventional two-wire smoke detectors must be UL compatible with the UL
listed monitor module. For the ULC listed monitor module, the conventional 2-
wire smoke detectors must be ULC compatible with the monitor module. A list
of compatible two-wire conventional detectors is available from Fire-Lite (P/N
15384).

PACKAGE CONTENTS

(1) Two-wire monitor module, P/N M302
(1) 3.9K ohm end-of-line resistor (A2143-10)
(1) Off-white cover plate
(1) Screw pack for cover plate

MOUNTING
The M302(A) monitor module mounts directly to a 4 inch square electrical box
as shown in Figure 2. The box must have a minimum depth of 2-1/8 inches.

WIRING
NOTE: All wiring must conform to applicable local codes, ordinances and reg-

ulations.

1. Install module wiring in accordance with the job drawings and appropriate

wiring diagrams (Figures 3 – 5).

2. Set the address on the module per job drawings.
3. Secure the module to the electrical box (supplied by installer), as shown in

Figure 2.

4. Perform steps one, two, and three for all modules.

F400-09-00

1

I56-631-06

Fire-Lite, 12 Clintonville Rd., Northford , CT 06472 (203) 484-7161

A78-1327-00

FIGURE 2.

EXPLODED VIEW OF TYPICAL MODULE

DETAILING MOUNTING ARRANGEMENT