Figure 9. c304 control module in relay output mode – Fire-Lite I300(A) User Manual

Page 4

background image

F300-03-01

4

I56-570-05

© Fire-Lite Alarms, Inc. 1996

A78-2287-04

FIGURE 10. I300 FAULT ISOLATOR MODULE WIRING

1 (–)

2 (+)

MODULE

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

CONTROL

CONNECT MODULES TO LISTED COMPATIBLE

9

8

7

6

5

3

4

RELAY COMMON

NORMALLY CLOSED

FORM "C" RELAY OPERATION WHEN

BOTH TABS J1 AND J2 ARE BROKEN.

J1 & J2

MODULE DOES NOT SUPERVISE CIRCUITS

CONTROLLED BY FORM C CONTACT.

NORMALLY OPEN

RELAY CONTACT RATINGS:

INDUCTIVE: 1 A @ 30 VDC (.6 PF)

RESISTIVE: 2 A @ 30 VDC

PILOT DUTY: .6 A @ 30 VDC (.35 PF)

.3 A @ 110 VDC (.35 PF)

.3 A @ 120 VAC (.35 PF)

C304(A)

CONTROL PANELS ONLY

PREVIOUS DEVICE

COMMUNICATION LINE

SEE FIRE-LITE PRODUCT

MANUAL FOR WIRE

SPECIFICATIONS

BREAK OFF TABS

J1 & J2 TO ENABLE

FORM C OPERATION

ALL WIRING SHOWN IS POWER LIMITED

(+)

(+)

(–)

1 (–)

2 (+)

1 (–)

2 (+)

(+)

(–)

(+)

(–)

1 (–)

2 (+)

1 (–)

2 (+)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

1 (–)

2 (+)

(+)

(–)

1 (–)

2 (+)

1 (–)

2 (+)

3 (–)

4 (+)

(–)

(+)

(+)

(–)

(–)

1 (–)

2 (+)

3 (–)

4 (+)

1 (–)

2 (+)

3 (–)

4 (+)

1 (–)

2 (+)

3 (–)

4 (+)

(+)

(–)

(+)

(–)

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED.

(+)

(–)

(+)

(–)

GROUPS OF ADDRESSABLE DEVICES ARE SEPARATED BY FAULT ISOLATOR

GROUP OF DEVICES IF A SHORT CIRCUIT OCCURS ON THE

SIGNALING LINE CIRCUIT WITHIN THAT GROUP.

A PAIR OF FAULT ISOLATOR MODULES WILL DISCONNECT A

FIRE-LITE UL LISTED COMPATIBLE

CONTROL PANEL

MODULES. ANY COMBINATION OF COMPATIBLE,

LISTED DEVICES MAY BE MIXED WITHIN A GROUP.

COMMUNICATION LINE

FAULT ISOLATOR

MODULE

I300(A)

FAULT ISOLATOR

MODULE

I300(A)

FAULT ISOLATOR

MODULE

I300(A)

FAULT ISOLATOR

MODULE

I300(A)

SEE FIRE-LITE PRODUCT

MANUAL FOR

WIRE SPECIFICATIONS

INSTALLATION WARNINGS AND NOTES
Control and isolator modules use a latching relay that can change states if it is subjected to mechanical shocks or jarring. As a
result, although modules are shipped with their relays in the open state, the contacts may have closed during shipment. Con-
necting an auxiliary control circuit to closed relay contacts in a control module can cause an unexpected, and possibly danger-
ous, activation of that circuit. Therefore, do NOT connect an auxiliary control circuit to the relay contacts before ensuring that
they are in their open (standby) state. Make sure that the contacts are open by allowing the control panel to poll the module at
least once, as indicated when the LED blinks.

If the contacts of several isolator modules are closed when system power is initially applied, it increases the load on upstream
modules, causing their relays to open. This prevents the proper application of power to the entire system. To correct this, con-
nect a temporary jumper between terminals 2 and 3 on all isolator modules whose LEDs are continuously lit OR interrupt the
signal line circuit after the last open isolator. The panel must delay communications for at least one minute after power is ap-
plied to allow all system devices to power up past the 7 volt threshold.

A78-2286-03

A78-1953-02

FIGURE 9. C304 CONTROL MODULE IN RELAY OUTPUT MODE