Fire-Lite I300(A) User Manual
Page 2
A78-2281-03
FIGURE 4. TYPICAL M300 FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D
1 (-)
2 (+)
MODULE
FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(-)
DEVICE
(+)
(-)
3 (-)
4 (+)
(+) 9
(-) 8
(-) 7
(+) 6
XXX 5
CONTROL
(-)
(+)
(-)
(+)
47K EOL
RESISTOR
A2143-00
UL LISTED EOL RELAY
SHOWN ENERGIZED
A77-716B
XXX - DO NOT
USE TERMINAL 5
TO NEXT CONTROL MODULE OR END
OF LINE RELAY (EOLR); ONE EOLR
REQUIRED PER BRANCH CIRCUIT
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
USE UL LISTED INDICATING APPLIANCES
RESISTIVE: 2 A @ 30 VDC
INDUCTIVE: 1 A @ 30 VDC (.6 PF)
PILOT DUTY: .6 A @ 30 VDC (.35 PF)
MAXIMUM LOAD:
SEE FIRE-LITE PRODUCT
MANUAL FOR
WIRE SPECIFICATIONS
BRANCH CIRCUIT
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE ON TERMINALS
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
(-)
(+)
ISOLATED, REGULATED
POWER SUPPLY, LISTED FOR FIRE
PROTECTION WITH BATTERY BACKUP
(MONITOR LOSS OF PRIMARY POWER)
C304(A)
FIRE-LITE CONTROL PANELS ONLY
INDICATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE W
COMMUNICATION LINE
PREVIOUS DEVICE
EXTERNAL POWER SOURCE MUST BE
POWER LIMITED PER NFPA 70
A78-2282-05
FIGURE 5. TYPICAL C304 INDICATING CIRCUIT CONFIGURATION, NFPA STYLE W
F300-03-01
2
I56-570-05
1 (–)
2 (+)
MODULE
FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
(–)9
(+)8
(+)7
(–)6
M300(A)
FIRE-LITE CONTROL PANELS ONLY
PREVIOUS DEVICE
COMMUNICATION LINE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9.
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USE. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICE ON THE SAME MODULE.
INITIATING DEVICE CIRCUIT - NFPA STYLE D
POWER LIMITED: 230
µ
A MAX @ 12 VDC MAX
IDC INSTALLATION WIRING SHALL NOT
EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
SEE FIRE-LITE PRODUCT
MANUAL FOR WIRE
SPECIFICATIONS
1 (–)
2 (+)
MODULE
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
SEE FIRE-LITE PRODUCT
MANUAL FOR WIRE SPECIFICATIONS
(–)9
(+)8
(+)7
(–)6
M300(A)
FIRE-LITE CONTROL PANELS ONLY
PREVIOUS DEVICE
COMMUNICATION LINE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
47 K EOL
RESISTOR
A2143-00
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
INITIATING DEVICE CIRCUIT - NFPA STYLE A OR B
POWER LIMITED: 230
µ
A MAX @ 12 VDC MAX
IDC INSTALLATION WIRING SHALL NOT
EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
A78-2280-05
FIGURE 3. TYPICAL M300 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE A OR B