Electrical Specifications

Product Description

1.5 Electrical Specifications

1.5.1 Power Requirements

Voltage for the ECC-FFT must be a UL-listed, power-limited, filtered, non-resettable nominal 24
VDC source. The voltage source must be within the range of 17-29 VDC.

1.5.2 Current Ratings

Maximum current ratings for determining backup battery requirements for alarm (active) and
standby conditions over the input voltage range of 17-29 VDC are shown in Table 1.3 below.

Zone 1-

Zone 8

Zone 9 -

Zone 16

Zone 17 -

Zone 24

Figure 1.2 ECC-FFT Keypad

e

cc

ff

tk

yp

d.

w

m

f

Circuits

Voltage

Current

SLC Circuit

32 V

150 mA

Audio Circuits

17 V

53 mA

Trouble Relay

12 VDC

1 A

Table 1.2 Electrical Ratings

Active

Standby

ECC-FFT

230 mA

120 mA

Table 1.3 ECC-FFT Current Draw