beautypg.com

Sample port, Vent port, Caution – Detcon 972-071170-0LC User Manual

Page 3

background image

2. Install a length of tubing from the desired sample point to the sample port as shown below. Sample draw tub-
ing should be either teflon or stainless steel 1/4" OD. Sample flow rates are set between 500 and 1000 ml/m.

CAUTION:

When detecting for NH3, CL2, CLO2, or HCL care must be taken to use a minimum amount of stainless steel tub-

ing and connections because stainless steel readily absorbs these gasses and will cause significant error in the detection process.
Teflon tubing is recommended for these applications.

3. Install a length of tubing from the vent port and an area deemed safe for vent as shown below.

Caution: Observe correct polarity when terminating all input/output wiring. Failure to do so may result in
circuit damage on power up. Seethe field wiring diagram below for terminal locations.

4. Connect 117VAC to the connector labeled “117VAC IN”.
5. If applicable, connect 24 VDC battery backup to the connector labeled “24 VDC IN”.
6. Connect signal loop to remote recording device, computer, or controller. The terminals are labeled

SENSOR “+” and “mA”.

Detcon Model 972-071170-0LC Gas Detection System PG.3

Sample

Port

0

100

200

300

400

500

CAL PORT

SET

FLOW

SAMPLE
PORT

detcon inc.
HOUSTON, TEXAS

SAMPLE DRAW

GAS DETECTION SYSTEM

Vent Port