DM-534C Oxygen Sensor Assembly

DM-534C O2 Sensor Instruction Manual Rev.1.4

Page 4 of 18

3.2

Interference Data

Table 1 Interference Data

Methane

100% = 0

Hydrocarbons

100% = 0

Hydrogen

100% = < 2%

Carbon Monoxide

20% = < 0.5%

4.0 SPECIFICATIONS

Method of Detection

Air battery diffusion/adsorption


Electrical Classification

Class I; Groups B, C, D; Div. 1.


Response Time (T90)

T90 < 20 seconds


Clearing Time

90% < 20 seconds


Repeatability

± 2% FS


Range

0-25% O2


Operating Temperature

-4° to +122° F


Accuracy

± 2% FS


Linearity

± 0.5% FS


Sensor Warranty

2 year conditional


Power Consumption

60 mA @ 24 VDC


Output

Linear 4-20 mA DC


Input Voltage

11.5-28 VDC

5.0 OPERATING SOFTWARE

Operating software is menu listed with operator interface via the two magnetic program switches located under
the face plate. The two switches are referred to as “PGM 1” and “PGM 2”. The menu list consists of 3 items
which include submenus as indicated below. (Note: see the end of this manual for a complete software flow
chart.)

1. Normal Operation

a) Current Status

2. Calibration Mode

a) Span

3. Program Menu

a) Program Status
b) Set Calibration Level