DM-534C Oxygen Sensor Assembly

DM-534C O2 Sensor Instruction Manual Rev. 1.4

Page 7 of 18

Drain

Conduit

"T"

EYS Seal Fitting

PGM 1

PGM 2

MODEL DM-534C

HOUSTON, TEXAS

FLT CAL

MicroSafe O2 Gas Sensor

ALM ALM

TM

Figure 6 Typical Installation

6.3

Local Electrical Codes

Sensor and transmitter assemblies should be installed in accordance with all local electrical codes. Use
appropriate conduit seals. Drains & breathers are recommended. The sensor assemblies are designed to meet
NEC and CSA requirements for Class I; Groups B, C, D; Div. 1 environments.

6.4

Accessibility

Consideration should be given to easy access by maintenance personnel as well as the consequences of close
proximity to contaminants that may foul the sensor prematurely.

Note: An appropriate conduit seal must be located within 18" of the sensor assembly.
Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose.


6.5

Installation Procedure

a) Remove the junction box cover and unplug the control circuit by grasping the two thumb screws and pulling
outward.
b) Securely mount the sensor junction box in accordance with recommended practice. See dimensional
drawing (Figure 7).