Detcon TP-624D User Manual
Page 42
Model TP-624D
TP-624D Instruction Manual
Rev. 0.4
Page 38 of 40
Operating Humidity:
5-100% RH (Non-condensing)
Operating Pressure:
Ambient ± 10%
Air Velocity:
0-5 meters/second
Mechanical Specifications
Mechanical Specifications
Dimensions:
10”H (including Splashguard) x 6.1”W x 4.3”D
(254mmH x 155mmW x 109mmD)
3 each ¾”NPT Female Input Ports
¼” Mounting Holes (J-box) 5.5” (140mm) Center to Center.
Weight:
6 lbs. (2.72kg) (with aluminum j-box)
9 lbs. (4.08kg (with Stainless Steel j-box)
Electrical Specifications
Input Voltage:
12-28 VDC
Power Consumption:
Normal operation = 68mA (<1.7 watt); Maximum = 85mA (2 watts)
RFI/EMI Protection:
Complies with ISO 92.0.01
Analog Output:
Linear 4-20mA DC current (1000 ohms maximum loop load @ 24VDC)
0mA
All Fault Diagnostics
2mA
In-Calibration
4-20mA
0-100% full-scale
22mA
Over-range condition
Serial Output:
RS-485 Modbus™ RTU
Baud Rate 9600 BPS (9600,N,8,1 Half Duplex)
Status Indicators:
4-digit LED Display with gas concentration,
full-script menu prompts for AutoSpan,
Set-up Options, and Fault Reporting
4 LEDs for Alarm 1, Alarm 2, Fault, and Calibration
Relay Outputs:
Alarm 1, Alarm 2, and Fault
5A @ 250VAC
5A @ 30VDC
Faults Monitored:
Heater Fault, Loop Fault, Input Voltage Fault, Sensor Fault,
Processor Fault, Memory Fault, Calibration Fault(s)
Cable Requirements:
Power/Analog – 3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
Serial Output – 2-wire twisted-pair shielded cable specified for RS-485 use.
Maximum distance is 4,000 feet to last sensor
I/O Protection:
Over-voltage, miswiring, EMI/RFI Immunity