Table 4 notation text string description – Detcon TP-624D User Manual
Page 33
Model TP-624D
TP-624D Instruction Manual
Rev. 0.4
Page 29 of 40
03/ 40014
Special #4
R/W
Function Dependant on Value
06
of 40006 (See Special Register
Table)
03 40015
Calibration Status
R
0x0000
Idle
0x0001
Zero Calibration Started
0x0002
Span Calibration Started
0x0003
Span Set
0x0004
Span Calibration Unsuccessful
06 40015
Calibration Enable
W
0x0001
Set Zero
0x0002
Set Span
0x0008
Signal simulation mode
0x0009
Set FP Bridge Voltage
0x000A
Set TP Heater Power
0x000B
Set IR Gain
03 40016 Read Text 1, first char in L
R
Two Char of Gas/Units String
6
03 40017
Read Text 2
R
Two Char of Gas/Units String
6
03 40018
Read Text 3
R
Two Char of Gas/Units String
6
03 40019
Read Text 4
R
Two Char of Gas/Units String
6
03 40020 Read Text 5, last char in H
R
Two Char of Gas/Units String
6
03
40021
Text null terminator in L
R
Two Char of Gas/Units String
6
03 40022
Special #5
R/W
Function Dependant on Value
of 40006 (See Special Register
Table)
03
40023 Processor Firmware Version
R
0x0102
Version 01.02
1
Units are determined by “units” field in the “notation” string
2
Span Gas must be less than or equal to Detectable Range and is usually about ½ of it.
3
Fault status bits self-reset when fault clears
4
Text in ASCII, in order L byte, H byte, L byte… See field descriptions of notation string.
Table 4 Notation Text String Description
Character #
1
2
3
4
5
6
7
8
9
10
11
Description
Units
0x20
Gas Type
0x00
Units – This field is ‘PPM’, ‘PPB’, or ‘_ _ %’ (where ‘ _ ‘ is a space, 0x20).
0x20 – The units field is terminated with an ASCII space (0x20)
Gas Type – This field contains the gas type of the cell (typically “H2S _ _ _”)
0x00 – The notation string is terminated with an ASCII null character