4. RS-485 Modbus
TM
Protocol
Model TP-624D sensors feature Modbus™ compatible communications protocol output and are addressable
via the program mode. Communication is via a two wire, half duplex RS-485, 9600 baud, 8 data bits, 1 stop
bit, no parity, with the sensor set up as a slave device. A master controller up to 4000 feet away can poll up to
256 different TP-624D sensors. This number may not be realistic in harsh environments where noise and/or
wiring conditions would make it impractical to place so many devices on the same pair of wires. If a multi-
point system is being utilized, each sensor should be set for a different address. Typical address settings are:
01, 02, 03, 04, 05, 06, 07, 08, 09, 0A, 0B, 0C, 0D, 0E, 0F, 10, 11…etc.
Sensor Serial ID numbers are factory default to 01. These can be changed in the field via the Operator
Interface described in Section 3.5.7.
The following table explains the details of the Modbus™ protocol that the TP-624D sensor supports.
Table 3 Modbus Registers
FC REG
Content Description
R/W
Content Definition
Value
Meaning
Range
03 40000
Device Type
R
8
700 Sensor
03
40001
Read Detectable Range
1,2
R/W
100
For 0-100
DM – 0 to 10000
06
40001
Write Detectable Range
10000
For 0-10000
2
FP – Read only
TP – 20, 50, 100, 200
IR – 0 to 10000
PI – 0 to 10000
03 40002
Read Concentration
3,2
R
1000
Bound by range. If > range, this
value is in fault.
03
40003
Read AutoSpan Level
4,2
R/W
50
Span gas at 50
DM – 1% to 95% of Range
06
40003
Write AutoSpan Level
FP – 5% to 95% of Range (40001)
TP – 2% to 50% of Range (40001)
IR – 5% to 95% of Range (40001)
PI – 1% to 95% of Range (40001)
03 40004
Read Sensor Life
R
85
For 85% sensor life
03 40005
Read Fault Status Bits
5
R
0x0001
Global Fault
0x0002
Auto Span Fault
0x0004
Temperature Fault
0x0008
4-20mA Fault
0x0010
Input Voltage Fault
0x0020
Memory Fault
0x0040
Processor Fault
0x0080
Clearing Fault
0x0100
Stability Fault
0x0200
Range Fault
0x0400
Sensor Fault
0x0800
Zero Fault
0x1 000
Sensor Fault 2
0x2000
0x4000
In Calibration
0x8000
Communication Error
03 40006
Read Model #
R
1, 2, 3, 4, 5
DM, FP, IR, TP, PID
respectively
03 40007
Read Days Since Cal
R
29
29days
03 40008
4-20 Current Output
mA x100
R
400
4.00mA
03 40009
Read Input Voltage
V x100
R
2400
24.00V
03 40010
Read Temperature
R
28
28 °C
03/
06
40011
Special #1
R/W
Function
Dependant
on
Value
of
40006
(See Special
Register
FC REG
Content Description
R/W
Content Definition
Value
Meaning
Range
03/ 40012
Special #2
R/W
Function Dependant on Value
06
of 40006 (See Special Register
Table)
03
40013
Special #3
R
Function Dependant on Value
of 40006 (See Special Register
Table)